18kw Split EVI Low Temperature Air to Water Heat Pump Split Air Source Heat Pump Heat Pump

PRODUCT DETAIL
Heating capacity:18kWEnergy source:electrical
type:Split EVI Cryogenic Heat PumpWorking temperature:Negative 25C-45C
Heat Exchanger:Shell and Tube Heat ExchangerSupply capacity:300 units per day
port:Guangzhou Huangpu, Guangzhou Nansha, Shenzhen, etc.Building Materials:Powder coating or stainless steel
Function:House Heating Cooling Hot Waterpower input:4.4kW
After-sales service provided:Free spare parts, on-site installation, on-site maintenance and repair servicesCertification:ce, CSA, EMC
Packaging Details:Plywood or cartonWarranty:2 years, 3 years
model:FA-06EVISpolice:3.61
compressor:Copelandpayment terms:L/C,Western Union,D/P,D/A,T/T,MoneyGram
Packaging Preview:place of origin; place of origin:China
application:outdoor, hotel, business, homeuse:Home use and commercial use
The refrigerant:R407CStorage/No Tanks:Instantaneous heater
color:whitebrand:francis
Install:Detached

Split Air to Water EVI Heat Pump

Model

FA-06EVIS

Heating capacity *

kilowatt

17.9

Heating power input *

kilowatt

4.4

Heating capacity**

kilowatt

13.4

Heating power input**

kilowatt

4.3

Heating capacity***

kilowatt

9.3

Heating power input***

kilowatt

4.2

police*

/

3.61

police**

/

3.12

police***

/

2.21

maximum. water temperature

°C

60

Rated water temperature

°C

55

water flow

m3/hour

2.73

water pressure drop

kPa

28

water connection

inch

1

Built-in water pump

/

Wilo RS 25/8

noise

dB(A)

55

compressor

Card

Copeland (EVI)

quantity

1

power supply

/

380V/3PH/50Hz

The refrigerant

/

R407C

Defrost type

/

reverse cycle

Net weight (outdoor unit)

Kilogram

120

Gross weight (outdoor unit)

Kilogram

135

Net size (outdoor unit)

mm

1110*460*1655

Package size (outdoor unit)

mm

1180*530*1800

Net weight (indoor unit)

Kilogram

30

Gross weight (indoor unit)

Kilogram

32

Net size (indoor unit)

mm

500*220*840

Package size (indoor unit)

mm

520*240*870

 

1. Working temperature of the unit: -25°C to 43°C
2. *Test conditions: Ambient temperature: 7°C/6°C, inlet/outlet: 30°C/35°C
** Test conditions: Ambient temperature: -2°C, water inlet/outlet: 30°C/35°C
*** Test conditions: Ambient temperature: -20°C, inlet/outlet: 30°C/35°C

 

 

 